Industrial networking made easy! www.anybus.com
Anybus® is a registered trademark of HMS Industrial Networks AB, Sweden, USA, Germany and other countries. Other marks and words belong to their respecve companies. All other
product or service names menoned in this document are trademarks of their respecve companies.
Part No: MMA104 Version 4 10/2011 - © HMS Industrial Networks - All rights reserved - HMS reserves the right to make modicaons without prior noce.
HMS Industrial Networks - Worldwide
HMS - Sweden (HQ)
Tel : +46 (0)35 17 29 00 (Halmstad HQ)
Tel: + 46 (0)35 17 29 24 (Västerås ofce)
E-mail: sales@hms-networks.com
HMS - China
Tel : +86 (0)10 8532 3183
E-mail: cn-sales@hms-networks.com
HMS - Denmark
Tel: +45 35 38 29 00
HMS - France
Tel: +33 (0)368 368 034
HMS - Germany
Tel: +49 721 989777-000
E-mail: ge-sales@hms-networks.com
HMS - India
Tel: +91 20 40111201
E-mail: in-sales@hms-networks.com
HMS - Italy
Tel : +39 039 59662 27
HMS - Japan
Tel: +81 (0)45 478 5340
E-mail: jp-sales@hms-networks.com
HMS - UK
Tel: +44 (0) 1926 405599
HMS - United States
Tel: +1 312 829 0601
E-mail: us-sales@hms-networks.com
Communicator CAN
Protocol Congurable CAN 1.0, 2.0A and 2.0B based protocols
Max stations 31 (with RS485/422)
Baud rate 20 kbit/s - 1 Mbit/s
Physical standards RS232/422/485
Technical Details Standard
Weight 150 g, 0,33 lb
Dimensions (L•W•H) 120•75•27 mm, 4,72•2,95•1,06”
Protection class IP20, NEMA rating 1
Enclosure material PC ABS, UL 94
Installation position Any
Mounting DIN rail (35•7,5/15) EN 50022
Certications
UL File number: E 203225 UL 508 Ind. Cont. Eq.
Hazardous Locations CLASS 1, DIVISION 2, GROUPS A, B, C AND D, T4 ANSI/ISA-12.12.01-2000
ATEX Zone 2, Cat 2 EN 60079-15
EN 60079-11
CE 2004/108/EC EN 61000-6-4
EN 61000-6-2
Electrical Characteristics
Power 24 VDC +/- 10 %
Current consumption Max 300 mA, Typical 100 mA
Hardware Characteristics
Reverse voltage protection Yes
Short circuit protection Yes
Galvanic isolation on subnetwork Yes
Environmental Characteristics
Operating temp -25 to 55
o
C, -13 to 131
o
F IEC 60068-2-1
IEC 60068-2-2
Storage temp -40 to 85
o
C, -40 to 185
o
F IEC 60068-2-1
IEC 60068-2-2
Relative Humidity 5-95 % non condensing IEC 60068-2-30
Installation altitude Up to 2 000 m
Immunity and emission for industrial environment
Electrostatic discharge +/- 4 kV EN 61000-4-2
Electromagnetic RF elds 10 V/m 80 MHz - 1 GHz
3 V/m 1,4 GHz - 2,0 GHz
1 V/m 2,0 GHz - 2,7 GHz
EN 61000-4-3
Fast Transients +/- 1 kV EN 61000-4-4
Surge protection +/- 1 kV EN 61000-4-5
RF conducted interference 10 V/rms EN 61000-4-6
Emission (at 10 m) 40 dB 30 MHz - 230 MHz
47 dB 30 MHz - 1 GHz
CISPR 16-2-3
Single Pack Accessories
• Resource CD • Conguration Cable (USB) Port • Installation sheet • Dsub with screw terminals for subnetwork
TECHNICAL SPECIFICATIONS
NETWORK SPECIFIC FEATURES
1 = Network connector, 2 = Baud rate,
3 = I/O data, 4 = Other
CANopen
1 = DSUB9M 2 = Up to 1 Mbit/s
3 = 512 byte IN/OUT 4 = Supports prole CIA DS301 V4.02
CC-Link
1 = 1*5p; 5.08 Phoenix Plug 2 = Up to 10 Mbit/s
3 = 128 IO points, 16 word IN/OUT 4 = Up to 4 occupied stations
ControlNet
1 = 2*BNC Coax + RJ45 (NAP) 2 = 5 Mbit/s
3 = 450 byte IN/OUT 4 = Communications adapter, prole n. 12
DeviceNet
1 = 1*5p; 5.08 Phoenix Plug 2 = 125-500 kbit/s
3 = 512 byte IN/OUT 4 = Communications adapter, prole n. 12
EtherCAT -
2 port
1 = 2*RJ45 2 = 100 Mbit/s
3 = 512 byte IN/OUT 4 = DS301 V4.02 compliant, 4 FMMU Channels
EtherNet/IP -
2 port
1 = 2*RJ45 2 = 10/100 Mbit/s 3 = 509/505 byte IN/OUT
4 = EtherNet/IP group 2 and 3 server. Modbus TCP slave functionality
Modbus RTU
1 = DSUB9F 2 = 1,2-57,6 kbit/s 3 = 512 byte IN/OUT 4 = RS232 and RS485
Modbus TCP -
2 port
1 = 2*RJ45 2 = 10/100 Mbit/s 3 = 512 byte IN/OUT
4 = Security framework
Probus
1 = DSUB9F 2 = Up to 12 Mb
3 = 244 IN/OUT (344 total) 4 = Probus DP (IEC 61158)
Pronet IO -
1 port
1 = RJ45 2 = 100 Mbit/s 3 = 512 byte IN/OUT
4 = RT Communication and Cyclic data exchange
Pronet IRT -
2 port
1 = 2*RJ45 2 = 100 Mbit/s 3 = 220 byte IN/OUT
4 = RT Communication and Support for I&M
The easy to use, visual based Anybus Conguraon Manager
contains pre-prepared funconality for CAN frame building
that gets your devices up and running in no me.
Power connector
with screw terminals
Status LEDs
Conguration switches
(if existing, behind lid)
Network connector
(see number 1 above)
DIN rail connector
Conguration port
CAN subnetwork
connector (DSUB 9-Pole
female)