Quantum Ethernet TCP/IP Modbus Application Protocol
840 USE 115 00 Version 1.0
81
The header is 7 b
tes lon
, and includes the followin
fields:
inv_id[2 b
tes] invocation id used for transaction pairin
proto_id[2 b
tes] used for intra-s
stem multiplexin
,default is 0 for Modbus
services
len[2 b
tes] the len field is a b
te count of the remainin
fields and
includes the dst_id and data fields.
The remainder of the pdu includes two fields:
dst_idx[1 b
te] destination index is used for intra-s
stem routin
of
packets.
currentl
not implemented
data[n b
tes] this is the service portion of the Modbus pdu, mb_pdu, and is
defined below
The service portion of the Modbus Application Protocol, called mb_pdu, contains 2
fields:
mb_pdu ::= { func_code[1], data[n] }
func_code[1 b
te] MB function code
data[n b
tes] this field is function code dependent and usuall
contains
information such as variable references, variable counts, and data offsets.
The size and content of the data field are dependent on the value of the function
code.
Comentários a estes Manuais