I/O Modules
674
35013379 02 October 2007
Fuse Locations The following figure shows the fuse locations for the DDO35301 module.
Fault Detection Group indication: Loss of field power/faulted point
Bus Current Required 250 mA max.
Power Dissipation 5 W (all points on)
External Power 19.2 ... 30 Vdc
Fusing
Internal 5A fuse for each group. Modicon Part # 043502405. For
the location of the fuses see Fuse Locations, p. 674.
External User discretion
Specifications
Possible danger to equipment or personnel.
Disconnect the supply voltage to the module and remove the field wiring terminal
strip to gain access to fuses.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
140
DDO 353 01
24 VDC OUT
X
Fuse Locations
Points
1-8
Points
9-16
Points
17-24
Points
25-32